CHECK LIST PREVENTIVE MAINTENANCE MECHANICAL ELECTRICAL
Protelindo Site ID Protlindo Site Name Date Time
WIB / WITA / WIT
Grounding Measurement : Ohm ( < 1 Ohm )Grounding Well : Ohm ( < 1 Ohm ) Tower Leg : Ohm ( < 1 Ohm ) Fence : Ohm ( < 1 Ohm ) Genset Tank : Ohm ( < 1 Ohm )
LIGHTING
FENCE
ENVA STATUS
PT NOKIA SIEMENS NETWORK( HARI )
Obstruction Light Failure : OK NOK N/A Remark : ( uninstalled, undetected ), …………. Grounding System : OK NOK N/A Remark : ( uninstalled, undetected ), …………. Fence Break : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), …………. Site Cleaning : OK NOK Remark : ( cleaning for grass / garbage )…………………… Flume Cleaning : OK NOK Remark : …………………… Paving Block or Gravel : OK NOK Remark : …………………… Barbared Wire : OK NOK Remark : …………………… Fence Door (Swing/Sliding) : OK NOK Remark : …………………… ENVA Check Respons Lightening Alarm : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Yard Lamp Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), …………. Site Photo Sensor : OK NOK N/A Remark : ( sensor respon checking ), …………. Yard Lamp Shield : OK NOK N/A Remark : ( lamp shield checking broken / no ), …….
4 Unit Yard Lamp Amount (Mercury & TL) :
TOWER
LIGHTING
Tower Lamp (OBL) Amount :0,33 0,36 N/A
……………………….
GROUNDING
……………………….: JAW-CJV-0004-D-P : TEMBALANG (SEMARANG) : 06/03/2012 : 10:18:00 AM
Base Service
CHECK LIST PREVENTIVE MAINTENANCE
MECHANICAL ELECTRICAL
BAR grounding tower : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… BAR grounding well : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… Down conductor Cable : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… Bolt Connection : OK NOK Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… Tower Type : SST Monopole Triangle Pole Mini Tower Painting Condition : OK NOK Remark : ( tower loosen paint 70 % ), GALVANIS Construction Condition : OK NOK Remark : ( paving down/ tower leg cracked ), …………. Tower Cleaning : OK NOK Remark : ( cleaning from spider nest / bee / etc ), …………. Tower Lamp / OBL : OK NOK N/A Remark : ( broken, cracked, unshielded), …………. Photo Sensor : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
Grounding Status : Lightening Rod : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
1 Unit Tower Lamp (OBL) Condition : OK NOK N/A Remark : ( broken, cracked, unshielded), ………….
INSPECTION BY
CHECK LIST PREVENTIVE MAINTENANCE
Protelindo Site ID Date Protlindo Site Name Time WIB / WITA / WIT Operator
B. R, S & T Indicator Lamps are lit : OK NOK NA MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..…… KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) :
V Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record : AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… KWH Box Including Pole KWH
:
OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition ) COS : OK NOK N/A Remark : ( clean, neat, broken ) PLN Power Supplied : kVA MCB input :
MCB Condition : OK NOK NA
1 Phase : A pcs
3 Phases : A pcs COS : A PLN ID : Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..…… Terminal / OKA : OK NOK NA ( Good Sealed ), ………..…… MCB : OK NOK NA ( Good Sealed ), ………..……
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
Measurement 0,39 0,37 0,53
211 378
Control Box : Ohm ( < 1 Ohm ) External Grounding Bar : Ohm ( < 1 Ohm ) Internal Grounding Bar : Ohm ( < 1 Ohm ) Base Frame Condition : OK NOK N/A Remark : ...............................
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
217 371
216 373
35037
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
52-3040397908
23 ……………… ………………
35
3
40
Dynabolt Condition : OK NOK N/A Remark : ............................... Base Frame Foundation : OK NOK N/A Remark : ...............................
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
Equipment Type
: OK NOK N/A Remark : ( uninstalled, undetected ), ………….
:
Indoor Outdoor AC Amount
:
2 unit AC Mark : Daikin National Others / PANASONIC 1,5 PK Broken AC YES NO YES NO YES NO YES NO Power 1,5 1,5 Pressure
70
70 Current Max Current Measurement AC Indoor Condition OK NOK OK NOK OK NOK OK NOK Pipe Condition OK NOK OK NOK OK NOK OK NOK Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A Switch Contactor OK NOK OK NOK OK NOK OK NOK AC Temperature Setting OK NOK OK NOK OK NOK OK NOK Room Temperature : Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK Shelter Roof : OK NOK N/A Remark : ( leak, broken ), ………….
Dinding Shelter
: OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), …………. Room Cleaning : OK NOK Leak Remark : …………………… Roof Cleaning : OK NOK Leak Remark : …………………… Benzoic Spreading
:
OK NOK Remark : ( cleaning for grass / garbage )…………………… Door Hinge Lubrication : OK NOK Remark : …………………… Shelter Foundation : OK NOK Remark : …………………… Heat Detector
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), …………. Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
6,72 8,28
Tenant
: JAW-CJV-0004-D-P : 06/03/2012 : TEMBALANG (SEMARANG) : 10:18:00 AM
: FLEXI
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
AC Status PK Psi
According with data signed at AC Outdoor
Ampere Leak / Not Leak Leak / Not Leak
Operation test switch < 24
o
C 20,7
PLN FUNCTION TEST
CHECK LIST PREVENTIVE MAINTENANCE
: JAW-CJV-0004-D-P : 06/03/2012 : TEMBALANG (SEMARANG) : 10:18:00 AM
Protelindo Site ID Date Protlindo Site Name Time WIB / WITA / WIT Operator
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
C
o
Operation test switch < 24
Ampere Leak / Not Leak Leak / Not Leak
According with data signed at AC Outdoor
AC Status PK Psi
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
: ISAT
Control Box : Ohm ( < 1 Ohm ) External Grounding Bar : Ohm ( < 1 Ohm ) Internal Grounding Bar : Ohm ( < 1 Ohm ) Base Frame Condition : OK NOK N/A Remark : ...............................
Measurement 0,37
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), …………. Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
: OK NOK N/A Remark : ( uninstalled, undetected ), ………….
OK NOK Remark : ( cleaning for grass / garbage )…………………… Door Hinge Lubrication : OK NOK Remark : …………………… Shelter Foundation : OK NOK Remark : …………………… Heat Detector
:
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), …………. Room Cleaning : OK NOK Leak Remark : …………………… Roof Cleaning : OK NOK Leak Remark : …………………… Benzoic Spreading
: OK NOK N/A Remark : ( cracked, leak, broken ), ………….
…………. unit AC Mark : Daikin National Others / …………….. Broken AC YES NO YES NO YES NO YES NO Power Pressure Current Max Current Measurement AC Indoor Condition OK NOK OK NOK OK NOK OK NOK Pipe Condition OK NOK OK NOK OK NOK OK NOK Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A Switch Contactor OK NOK OK NOK OK NOK OK NOK AC Temperature Setting OK NOK OK NOK OK NOK OK NOK Room Temperature : Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK Shelter Roof : OK NOK N/A Remark : ( leak, broken ), …………. Dinding Shelter
:
Indoor Outdoor AC Amount
:
Equipment Type
Tenant
- N/A
V Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record : AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… KWH Box Including Pole KWH
212 212 212
Dynabolt Condition : OK NOK N/A Remark : ............................... Base Frame Foundation : OK NOK N/A Remark : ...............................
40
1 …………… …………..
35
7,7
N/A
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
2472
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
:
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) :
B. R, S & T Indicator Lamps are lit : OK NOK NA MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..…… KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
MCB in the KWH 'ON' Position
KWH Record : OK NOK NA ( Good Sealed ), ………..…… Terminal / OKA : OK NOK NA ( Good Sealed ), ………..…… MCB : OK NOK NA ( Good Sealed ), ………..……
3 Phases : A pcs COS : A PLN ID : Seal
1 Phase : A pcs
MCB Condition : OK NOK NA
OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition ) COS : OK NOK N/A Remark : ( clean, neat, broken ) PLN Power Supplied : kVA MCB input :
PLN FUNCTION TEST
CHECK LIST PREVENTIVE MAINTENANCE
Protelindo Site ID Date Protlindo Site Name Time WIB / WITA / WIT Operator
Measurement 0,33 0,42
:
OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection / pole Condition ) COS : OK NOK N/A Remark : ( clean, neat, broken ) PLN Power Supplied : kVA MCB input :
MCB Condition : OK NOK NA
1 Phase : A pcs
3 Phases : A pcs COS : A PLN ID : Seal
KWH Record : OK NOK NA ( Good Sealed ), ………..…… Terminal / OKA : OK NOK NA ( Good Sealed ), ………..…… MCB : OK NOK NA ( Good Sealed ), ………..……
MCB in the KWH 'ON' Position
A. Current flows to the MCCB for Devices : OK NOK NA ( Current Measurement result = Visual check ), ………..……
B. R, S & T Indicator Lamps are lit : OK NOK NA MCB for Devices to 'ON' Position : OK NOK NA ( MCB In position ), ………..…… KWH Meter Spin Normally : OK NOK NA ( Spin Normally ), ………..……
N/A
Phase Voltage R - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage S - T (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage S - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage T - R (350V - 400V) : V 380 V +/- 5% max 10 V Phase Voltage T - N (200V - 240V) : V 220 V +/- 5% max 10 V Phase Voltage G - N (< 5 V) :
OUTDOOR TYPE
KWH ELECTRICAL MEASUREMENT
212 213 212
1311
ELECTRICAL VISUAL CHECK
PLN VISUAL CHECK
N/A
7,7
16
2 …………… ……………
40
V Phase Voltage R - S (350V - 400V) : V 380 V +/- 5% max 10 V KWH Meter Record : AC-PDB : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), ……… KWH Box Including Pole KWH
Dynabolt Condition : OK NOK N/A Remark : ............................... Base Frame Foundation : OK NOK N/A Remark : ...............................
Equipment Type
Tenant
:
Indoor Outdoor AC Amount
:
…………. unit AC Mark : Daikin National Others / …………….. Broken AC YES NO YES NO YES NO YES NO Power Pressure Current Max Current Measurement AC Indoor Condition OK NOK OK NOK OK NOK OK NOK Pipe Condition OK NOK OK NOK OK NOK OK NOK Auto Restart OK NOK N/A OK NOK N/A OK NOK N/A OK NOK N/A Switch Contactor OK NOK OK NOK OK NOK OK NOK AC Temperature Setting OK NOK OK NOK OK NOK OK NOK Room Temperature : Exhaust Fan Condition : OK NOK Exhaust Fan Cleaning : OK NOK Shelter Roof : OK NOK N/A Remark : ( leak, broken ), …………. Dinding Shelter
: OK NOK N/A Remark : ( cracked, leak, broken ), ………….
Fence Condition : OK NOK N/A Remark : ( collapsed, broken ), …………. Room Cleaning : OK NOK Leak Remark : …………………… Roof Cleaning : OK NOK Leak Remark : …………………… Benzoic Spreading
:
OK NOK Remark : ( cleaning for grass / garbage )…………………… Door Hinge Lubrication : OK NOK Remark : …………………… Shelter Foundation : OK NOK Remark : …………………… Heat Detector
: OK NOK N/A Remark : ( uninstalled, undetected ), ………….
Smoke Detector : OK NOK N/A Remark : ( uninstalled, undetected ), …………. Ring Bell : OK NOK N/A Remark : ( uninstalled, undetected ), ………….
: JAW-CJV-0004-D-P : 06/03/2012 : TEMBALANG (SEMARANG) : 10:18:00 AM
Control Box : Ohm ( < 1 Ohm ) External Grounding Bar : Ohm ( < 1 Ohm ) Internal Grounding Bar : Ohm ( < 1 Ohm ) Base Frame Condition : OK NOK N/A Remark : ...............................
: TSEL
AIR CONDITIONER
Measurement Remark AC # 1 AC # 2 AC # 3 AC # 4
AC Status PK Psi
According with data signed at AC Outdoor
Ampere Leak / Not Leak Leak / Not Leak
Operation test switch < 24
o
C
EXHAUST FAN
SHELTER
Alarm System
GROUNDING
Grounding Status : OK NOK N/A Remark : ( uncompleted condition / stolen / broken / worse connection ), …… ...
PLN FUNCTION TEST
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCE
PHOTO REPORT
Base Service Foto A - 1
Foto A - 2
Tampak halaman site sebelum dibersihkan Tampak halaman site setelah dibersihkan
Foto A - 3Foto A - 4
Tampak tower bagian atas (tampak mounting & lampu halaman) Tampak tower bagian bawah (tampak pedestal/kaki tower)
Foto A - 5Foto A - 6
Tampak pagar / tembok Tampak paving block / gravel
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCE
PHOTO REPORT
Base Service Foto B - 1
Foto B - 2 Status grounding - Tampak lightning rod (Splitzen) Status grounding - Grounding ke Pagar Foto B - 5
Foto B - 6
Pengukuran grounding - Grounding ke Pagar Pengukuran grounding - Grounding ke kaki tower
Foto B - 3Foto B - 4 Status grounding - Down Conductor cable Status grounding - Bolt Connection
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK
PREVENTIVE MAINTENANCE
PHOTO REPORT
Base Service Foto C - 1
N/A
Foto C - 2 Pengukuran grounding - Tangki genset (if any) Pengukuran grounding - Box control
Tampak Access Lease Area Site View - Tampak Atas (Sisi -1)
Foto C - 3 Foto C - 4OBL - Berfungsi dengan baik Yard Lamp - Berfungsi dengan baik
Foto C - 5 Foto C - 6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Contractor : NOKIA SIEMENS NETWORK Site View - Tampak Atas (Sisi - 2) Safety Tools (Safety belt, helm, sepatu, sarung tangan)
PREVENTIVE MAINTENANCE
PHOTO REPORT
Base ServiceFoto D - 1 Foto D - 2
N/A
Foto D - 5 Foto D - 6 Foto D - 3 Foto D - 4 Tampak warning sign board (if any)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto A-1
Foto A-2 Tampak Bagian Luar Shelter Tampak Bagian Dalam Shelter Foto A-3
Foto A-4 Tampak Cable Tray Tampak Lampu di dalam shelter Foto A-6
Foto A-5
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI
Tampak Grounding di dalam shelter Tampak pondasi shelter
PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto B-1
Foto B-2 Foto B-5
Foto B-6 Foto B-3 Foto B-4
Tampak Fire Extinguisher Tampak Panel Alarm
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI Foto C-1
Foto C-2 Tampak AC Indoor Tampak AC Outdoor PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor
Pengukuran - Tekanan AC Pengukuran - Temperature Shelter Foto C-5
Foto C-6 Foto C-3 Foto C-4
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto D-1
Foto D-2 Pengukuran - Tegangan T - N (Panel KWH) Pengukuran - Tegangan R - S (Panel KWH) Foto D-3
Foto D-4 Pengukuran - Tegangan S - T (Panel KWH) Pengukuran - Tegangan R - T (Panel KWH) Foto D-5
Foto D-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI Pengukuran - Tegangan S - N (Panel ACPDB) Pengukuran - Tegangan T - N (Panel ACPDB)
PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto D-1
Foto D-2 Foto D-3
Foto D-4 Pengukuran - Tegangan R - S (Panel ACPDB) Pengukuran - Tegangan S - T (Panel ACPDB) Foto D-5
Foto D-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto E-1
Foto E-2 Status grounding - Control Box Status grounding - External Grounding Bar Foto E-3
Foto E-4
Status grounding - Internal Grounding Bar Pengukuran grounding - Control Box
Foto E-5Foto E-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI Tampak Pole KWH Box Kondisi KWH Panel (Keadaan tertutup)
PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto F-1
Foto F-2 Foto F-5
Foto F-6 Foto F-3 Foto F-4 Kondisi KWH Panel (Keadaan terbuka) Kondisi MCB KWH Meter
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : FLEXI PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Indoor Foto G-1
Foto G-2 Kondisi segel pada MCB KWH meter KWH meter record Foto G-5
Foto G-6 Foto G-3 Foto G-4
ID Pelanggan
Protelindo ID : JAW-CJV-0004-D-P Date Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto A-1
Foto A-2
Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt
: 06/03/2012Foto A-3 Foto A-4 Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH)
Foto A-6 Foto A-5
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)
PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto B-1
Foto B-2 Foto B-5
Foto B-6 Foto B-3 Foto B-4
Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT Foto C-1
Foto C-2 Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB) PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor
Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)
Foto C-5Foto C-6 Foto C-3 Foto C-4
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto D-1
Foto D-2
Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar
NAFoto D-3 Foto D-4 Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar
Foto D-5 Foto D-6
NA
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT
Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)
PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto E-1
Foto E-2 Foto E-5
Foto E-6 Foto E-3 Foto E-4 Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : ISAT Foto F-1
N/A
Foto F-2 KWH meter record
ID Pelanggan PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor
Foto F-5 Foto F-6 Foto F-3 Foto F-4
Protelindo ID : JAW-CJV-0004-D-P Date Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor : 06/03/2012 Foto A-1
Foto A-2
Tampak Kondisi Base Frame Tampak Kondisi Dyna Bolt
Foto A-3Foto A-4 Tampak Pondasi Base Frame Pengukuran - Tegangan R - N (Panel KWH) Foto A-6
Foto A-5
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto B-1
Foto B-2
Pengukuran - Tegangan R - S (Panel KWH) Pengukuran - Tegangan S - T (Panel KWH)
Foto B-3Foto B-4
Pengukuran - Tegangan R - T (Panel KWH) Pengukuran - Tegangan G- N (Panel KWH)
Foto B-5Foto B-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto C-1
Foto C-2 Pengukuran - Tegangan T - N (Panel ACPDB) Pengukuran - Tegangan R - S (Panel ACPDB) Foto C-3
Foto C-4
Pengukuran - Tegangan S - T (Panel ACPDB) Pengukuran - Tegangan R - T (Panel ACPDB)
Foto C-5Foto C-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto D-1
Foto D-2
Status grounding - External Grounding Bar Status grounding - Internal Grounding Bar
NAFoto D-3 Foto D-4 Pengukuran grounding - Control Box Pengukuran grounding - External Grounding Bar
Foto D-5 Foto D-6
NA
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto E-1
Foto E-2
Kondisi KWH Panel (Keadaan tertutup) Kondisi KWH Panel (Keadaan terbuka)
Foto E-3Foto E-4 Kondisi MCB KWH Meter Kondisi Segel pada Terminal KWH Foto E-5
Foto E-6
Protelindo ID : JAW-CJV-0004-D-P Date : 06/03/2012 Protelindo Name : TEMBALANG (SEMARANG) Tenant : TSEL PREVENTIVE MAINTENANCE PHOTO REPORT Tenant Outdoor Foto F-1
N/A
Foto F-2 KWH meter record
ID Pelanggan
Foto F-3 Foto F-4
Foto F-5 Foto F-6