Large unsaturated zone Directory UMM :Data Elmu:jurnal:A:Advances In Water Resources:Vol21.Issue6.1998:

8.3 Large unsaturated zone

In order to test the variable substitution strategies, the pro- blem shown in Fig. 16 was used. Note that this problem has a large unsaturated zone, with hydrostatic pressure con- ditions on the left and right hand boundaries location of water table as indicated in Fig. 16. This is a cross-section, with thickness 0.25 m in the direction normal to the cross- section. The domain was discretized using a 16 3 11 grid, Dx ¼ Dz ¼ 0.25 m. The data in Table 3, Table 5 and Table 6 were used. In addition, another set of relative permeability and capillary pressure data was tested Table 7 and Table 8. The data in these tables is representative of a Borden sand 47 . In parti- cular, the capillary pressure data is based on the dimension- less capillary pressure curves in Ref. 48 . A number of cases were tested, using both LNAPL and DNAPL data Table 4, and both equilibrium eqn 2 and nonequilibrium eqn 4, eqn 5, eqn 7 assumptions. The problem was initially fully saturated, and was run to 7 days with no NAPL injection to equilibrate the unsaturated flow model. From 7.0 to 7.1 days, a NAPL contaminant was injected at a rage of 0.153 m 3 day. Injection then ceased, and the simulation was run to 500 days. 9 TEST RESULTS 9.1 LIQUID_STATE variable substitution As discussed previously, variable substitution for LIQUID_STATE primary variables is not actually required since P n can be used as a primary variable without switching to S w . However, in 26 , it was demonstrated that this type of variable switching speeded up the convergence of the Newton iteration for unsaturated flow problems under very dry conditions. Sometimes an order of magnitude improvement in number of Newton iterations was observed 26 . However, this improvement was only seen for very dry conditions, where the capillary pressure– saturation curve had a very large derivative. We did not anticipate this type of problem for multi-phase passive air phase simulations, since we were mainly inter- ested in problems near and below the water table, which have water saturations well above the critical value, due to the capillary fringe. However, rather to our surprise, we found that variable substitution had a large effect for simu- lations involving a NAPL phase. As a first example, consider the LNAPL Problem Section 8.1. Two runs were carried out. The first run disabled the LIQUID_STATE variable substitution eqn 27 by setting tol f ¼ tol b ¼ ¹` see eqn 27, in which case P n was always the primary variable. The second run used the vari- able switching parameters tol f ¼ 0.99 and tol b ¼ 0.9. This problem was run to a stopping time of 11 days. Full Newton iteration was used with a van Leer flux limiter. There was virtually no difference between these two methods during the initial part of the run to 7 days, which was simply an unsaturated flow situation no NAPL. The run using LIQUID_STATE switching used 72 Newton iterations, compared with 80 Newton iterations for the run without LIQUID_STATE switching, to complete the initial 7 days. This indicates that the initial unsaturated flow part of this scenario is not particularly difficult, in contrast to the situa- tion in 26 . This is to be expected since the capillary pressures do not have the large derivatives with respect to saturation, Fig. 16. Computational domain for test of variable substitution. Table 7. NAPL: water data: data set 2 S w k rw k rn P cnw kpa 0.074 0.0 0.45 9.4 0.1 0.001 0.42 7.0 0.2 0.005 0.34 4.2 0.3 0.025 0.28 3.3 0.4 0.05 0.22 2.8 0.5 0.08 0.17 2.5 0.6 0.14 0.115 2.2 0.7 0.22 0.065 2.0 0.8 0.36 0.025 1.9 0.85 0.46 0.01 1.85 0.9 0.57 0.0 1.8 1.0 1.0 0.0 0.0 Table 8. Liquid–gas data: data set 2 S w þ S n k ra k rn P can kpa P caw kpa 0.074 0.65 0.0 9.0 11.8 0.1 0.6 0.0 5.0 6.1 0.2 0.45 0.02 3.1 4.5 0.3 0.34 0.005 2.4 3.8 0.4 0.25 0.09 2.0 3.4 0.5 0.18 0.13 1.75 3.0 0.6 0.12 0.17 1.5 2.8 0.7 0.07 0.22 1.25 2.6 0.8 0.03 0.28 1.0 2.5 0.9 0.0033 0.35 0.9 2.4 0.92 0.0012 0.37 0.88 2.38 0.95 0.0 0.4 0.85 2.35 1.0 0.0 0.45 0.0 0.0 S n ¼ 0.1. Nonlinear multiphase flow 443 as in 26 . The run statistics for the complete run to 11 days are shown in Table 9. Clearly, the use of LIQUID_STATE variable substitution has a very large effect on performance after the NAPL is present in the system. At this point, we changed the input data to try to deter- mine the cause of this problem. Problems disappeared, for example, when P cnw ¼ 0.0, and when the P caw and P can were changed to straight line curves. Consequently, this problem definitely appears to be due to the non-linearities in the capillary pressure curves. Adjusting the value of S n in eqn 11 occasionally caused improvement, but sometimes made matters worse. It would therefore appear that the switching between P can and P caw as in eqn 9 was not the primary source of the problem. Note that other models of the two-phase to three-phase capillary pressure transition are similar in spirit. For example in 11 a P caw curve is used when no NAPL is present, and the three-phase P cnw curve is used for situations where free NAPL is present. For cases where the NAPL is trapped i.e. below residual, a weighted average of water- and gas-phase pressures is used for P n . An extensive series of tests was carried out to determine the range of liquid saturations where the LIQUID_STATE switching was effective, and where it ceased to be effective. The results are summarized in Table 10. Rather surprisingly, there was little effect on the number of Newton iterations for the parameters eqn 27, until an increase was observed at a value of tol f , tol b ¼ 0.4, 0.3. Lowering tol f , tol b any further caused the number of Newton iterations to increase to the number observed when the LIQUID_STATE switch- ing was entirely disabled. Consequently, it would appear that it is necessary to use saturations as primary variables until the liquid saturation is above 0.5. Since the problem in convergence seems to occur near the water table, this suggests that convergence difficul- ties are encountered as the NAPL phase becomes mobile at a given node, but this is not entirely clear. The safest choice of parameters appears to be use a value of tol f which is as large as possible. In the following, we will use tol f ¼ 0.99 and tol b ¼ 0.9. To study the effect of LIQUID_STATE switching in more detail, a comprehensive series of tests was carried out using the Large Unsaturated Zone problem see Section 8.3. If the LIQUID_STATE switching mechanism was enabled, we used the following parameters for tol f and tol b in eqn 27. tol f ¼ 0:99 tol b ¼ 0:9: 33 Full Newton iteration was used with a van Leer flux limiter. A number of cases were tested, using both LNAPL and DNAPL data Table 4, and both equilibrium eqn 2 and nonequilibrium eqn 4, eqn 5, eqn 7 assumptions. In addition, another set of relative permeability and capil- lary pressure data was tested Tables 7 and 8. The total Newton iteration counts for these tests are given in Table 11 CPU time roughly proportional to Newton iteration count. The total iteration counts are given for the complete run to 500 days. These tests indicate that LIQUID_STATE variable sub- stitution is always faster in terms of Newton iteration count than not using LIQUID_STATE switching. The decrease in Newton iteration count varies from more than a factor of 10 to less than a factor of 2. The increase in efficiency obtained using LIQUID_STATE switching is clearly highly dependent on the physical properties data, and on the modelling assumptions i.e. equilibrium, none- quilibrium. However, in all cases involving LNAPLs, dis- abling the LIQUID_STATE state switching increased the number of Newton iterations by more than a factor of 5. We have seen the same results in many tests. LIQUID_STATE state variable substitution is never signif- icantly slower than using P n as a primary variable, and is sometimes an order to magnitude faster. We emphasize that this is a different effect form that in 26 , since the work in 26 considered unsaturated flow in very dry soils. In the problems in this work, the capillary pressure data for two-phase Table 9. Performance of variable switching: LNAPL example, nonequlibrium model, stopping time 11 days Variable substitution method Total Newton iterations Normalized CPU time LIQUID_STATE switching 405 1.0 No LIQUID_STATE switching 1298 2.96 Table 10. Performance of variable switching: effect of switch- ing parameters: CPU time proportional to Newton iteration count tol f , tol b Total Newton iterations 0.9, 0.8 433 0.8, 0.7 409 0.7, 0.6 405 0.6, 0.5 489 0.5, 0.4 483 0.4, 0.3 1118 Table 11. Total Newton iteration count for test of LIQUID_STATE switching Fig. 16: CPU time proportional to Newton iteration count Scenario Switching No switching Data in Tables 5 and 6 Equilibrium LNAPL 160 2506 DNAPL 163 2703 Nonequilibrium LNAPL 205 1199 DNAPL 142 1472 Data in Tables 7 and 8 Equilibrium LNAPL 205 1199 DNAPL 228 707 Nonequilibrium LNAPL 169 1064 DNAPL 177 332 444 P. A. Forsyth et al. air–water flow does not give rise to convergence pro- blems, since the number of Newton iterations is virtually the same for both LIQUID_STATE switching and no LIQUID_STATE switching runs, before the NAPL is injected. Convergence difficulties arise only when the NAPL is injected. Although the cure for convergence problems is similar to that used in 26 , the cause of these problems appears to be different. In the following examples, we will always use LIQUID_STATE variable substitution.

9.2 Jacobian selection for the flux limiter: experiments