13.3.4 Earth Loop Impedance
A key factor in the design and choice of earth continuity conductors, e.g. cable armouring, bonding straps, and fault current protective devices is the ‘earth loop impedance’. This is especially the case for solidly earthed low voltage systems, whether they be three-phase, single-phase or even direct current systems.
The earth loop impedance is the total impedance seen by the source of voltage in a faulted circuit which involves the earthing conductors. Figure 13.10 shows the situation for a three-phase cable supplying a load such as a motor or static load.
Figure 13.10 Earth loop impedance of a three-phase circuit.
HANDBOOK OF ELECTRICAL ENGINEERING
Figure 13.11 Equivalent circuit of the earth return paths in the earth loop impedance circuit involving a cable and its armouring. This is an interpretation of BS7430 Clause 3.13.
The worst design case is shown wherein the fault occurs at the far end of the cable. The fault is assumed to be a line-to-earth fault having zero fault impedance. The equivalent circuit for this example is shown in Figure 13.11.
A pessimistic assumption can be made that the steelwork impedance Z e between the fault and the source is large compared with the parallel-connected cable armouring impedance Z a . This implies that the current will only return to the source through the cable armouring and the copper bonding connection, of impedance Z b , at the source-end of the cable. The impedance Z b includes the local steelwork at the source. The bonding is assumed to be in tact and of very low impedance compared with Z a . Hence Z b can be ignored, and so earth loop impedance Z loop simply becomes:-
Z loop =Z s +Z c +Z a ohms
The driving voltage is the phase voltage. The source impedance Z s is fixed and is usually that of the upstream supply cables and transformers, or generators (or the output impedance of supplies such as a UPS). Z s can often but not always be neglected. The cable conductor impedance Z c is easily calculated from the cable data for one phase conductor and its route length. Similarly the armouring impedance Z a can be calculated from the data, which is predominantly resistive for most types of power cables. For typical cable data see the tables in Chapter 9.
In order to safeguard against electric shock at the far end of the cable, where the AC root mean square voltage may exceed 50 V, the earth loop impedance must be limited to a particular value. This value is such that the fault current should only be passed by the protective device at the supply for a specific period of time, i.e. to satisfy the I -squared-t criterion given in sub-section 13.1.1. The correlation of loop impedance, current and time varies with the type of protective device, e.g. fuse,
EARTHING AND SCREENING
moulded case circuit breaker, miniature circuit breaker. The international standards such as IEC 60364 and Reference 10 give tables for the limiting values of the earth loop impedance for common ratings of fuses and circuit breakers. Once the limiting value for the circuit is determined from these tables it is a simple calculation procedure to find the maximum length of the cable that can be allowed, as demonstrated in 9.4.3.6.
Parts
» For Practitioners in the Oil, Gas and Petrochemical Industry
» CLASSIFICATION OF GAS TURBINE ENGINES
» ENERGY OBTAINED FROM A GAS TURBINE
» POWER OUTPUT FROM A GAS TURBINE
» Open-loop Speed-torque Characteristic
» Load Sharing between Droop-governed Gas Turbines
» MATHEMATICAL MODELLING OF GAS TURBINE SPEED GOVERNING SYSTEMS
» SIMPLIFIED THEORY OF OPERATION OF A GENERATOR
» ACTIVE AND REACTIVE POWER DELIVERED FROM A GENERATOR
» CONSTRUCTION FEATURES OF HIGH VOLTAGE GENERATORS AND INDUCTION MOTORS
» PRINCIPLE OF OPERATION OF THE THREE-PHASE MOTOR
» CONSTRUCTION OF INDUCTION MOTORS
» CABLE VOLT-DROP CONSIDERATIONS
» METHODS OF STARTING INDUCTION MOTORS
» THREE-PHASE TRANSFORMER WINDING ARRANGEMENTS
» CONSTRUCTION OF TRANSFORMERS
» Restarting and Reaccelerating of Motors
» Micro-computer Based Systems
» MOULDED CASE CIRCUIT BREAKERS
» ELECTRICALLY CONDUCTING MATERIALS USED IN THE CONSTRUCTION OF CABLES
» ELECTRICALLY NON-CONDUCTING MATERIALS USED IN THE CONSTRUCTION OF CABLES
» COMPOSITION OF POWER AND CONTROL CABLES
» CURRENT RATINGS OF POWER CABLES
» CABLES WITH ENHANCED PERFORMANCE
» ELEMENTS OF HAZARDOUS AREA CLASSIFICATION
» TYPES OF PROTECTION FOR HAZARDOUS AREAS
» CERTIFICATION OF HAZARDOUS AREA EQUIPMENT
» NON-CONSTANT VOLTAGE SOURCES – ALL VOLTAGE LEVELS
» CALCULATION OF FAULT CURRENT DUE TO FAULTS AT THE TERMINALS OF A GENERATOR
» CALCULATE THE SUB-TRANSIENT SYMMETRICAL RMS FAULT CURRENT CONTRIBUTIONS
» APPLICATION OF THE DOUBLING FACTOR TO FAULT CURRENT
» COMPUTER PROGRAMS FOR CALCULATING FAULT CURRENTS
» INTRODUCTION TO OVERCURRENT COORDINATION
» FEEDER TRANSFORMER PROTECTION
» BUSBAR PROTECTION IN SWITCHBOARDS
» HIGH VOLTAGE INDUCTION MOTOR PROTECTION
» LOW VOLTAGE INDUCTION MOTOR PROTECTION
» MATHEMATICAL EQUATIONS FOR REPRESENTING STANDARD, VERY AND EXTREMELY INVERSE RELAYS
» Low Voltage Three-Phase Systems
» IEC Types of Earthing Systems
» CONSTRUCTION DETAILS RELATING TO EARTHING
» SCREENING AND EARTHING OF CABLES USED IN ELECTRONIC CIRCUITS
» ELECTRICAL SUBMERSIBLE PUMPS
» CONTROL SYSTEMS FOR AC MOTORS
» HARMONIC CONTENT OF THE SUPPLY SIDE CURRENTS
» FILTERING OF POWER LINE HARMONICS
» AC UNINTERRUPTIBLE POWER SUPPLIES
» THE PURPOSE OF SPECIFICATIONS
» A TYPICAL FORMAT FOR A SPECIFICATION
» Application of Three-phase Short Circuit
» Derivation of an Equivalent Circuit
» Contribution of Three-phase Short-circuit Current from Induction Motor
» INTERNATIONAL ELECTRO-TECHNICAL COMMISSION (EUROPE)
» BRITISH STANDARDS INSTITUTION (UK)
» APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS
» ELECTRICAL POWER SYSTEM DEVICE NUMBERS AND FUNCTIONS
Show more