Hasil pengukuran suhu inti dan isolasi kabel dalam PVC 1.5 inchi

5. Hasil pengukuran suhu inti dan isolasi kabel dalam PVC 1.5 inchi

Tebal isolasi = 2.07 mm I = 11 A Waktu Menit Suhu pengukuran inti o C Rata-rata o C 1 2 3 25 25 25 25 5 49.2 49.5 49.3 49.3333 10 52.6 52.5 52.7 52.6 15 53.8 53.5 53.6 53.6333 20 54.3 54.1 53.9 54.1 25 54.5 54.3 54.5 54.4333 30 54.8 54.9 54.7 54.8 35 54.7 55.5 55.2 55.1333 40 54.7 55.5 55.7 55.3 45 55.5 55.5 55.6 55.5333 50 55.6 55.6 55.7 55.6333 55 55.7 55.7 55.7 55.7 60 55.7 55.7 55.7 55.7 65 55.7 55.7 55.7 55.7 70 55.7 55.7 55.7 55.7 75 55.7 55.7 55.7 55.7 Tebal isolasi = 2.07 mm I = 11 A Waktu Menit Suhu pengukuran isolai o C Rata-rata o C 1 2 3 25 25 25 25 5 43.7 44.2 43.4 43.7667 10 45.8 45.7 45.4 45.6333 15 47.4 47.8 47.9 47.7 20 48.4 48.5 48.9 48.6 25 49.5 49.5 49.6 49.5333 30 50.6 49.8 50.7 50.3667 35 51.3 51.6 51.2 51.3667 40 51.6 51.9 51.9 51.8 45 52.1 52.2 52.4 52.2333 50 52.5 52.6 52.6 52.5667 55 52.6 52.7 52.7 52.6667 60 52.7 52.8 52.7 52.7333 65 52.7 52.8 52.7 52.7333 70 52.7 52.8 52.7 52.7333 75 52.7 52.8 52.7 52.7333 80 52.7 52.8 52.7 52.7333 85 52.7 52.8 52.7 52.7333 90 52.7 52.8 52.7 52.7333 Universitas Sumatera Utara Tebal isolasi = 2.62 mm I = 11 A Waktu Menit Suhu pengukuran inti o C Rata-rata o C 1 2 3 25 25 25 25 5 47.8 47.4 47.6 47.6 10 48.8 48.6 48.9 48.7667 15 49.1 49.6 49.7 49.4667 20 49.5 50.6 50.7 50.2667 25 49.7 51.8 51.9 51.1333 30 50.8 52.1 52.3 51.7333 35 51.9 52.3 52.4 52.2 40 52.1 52.4 52.4 52.3 45 52.2 52.4 52.5 52.3667 50 52.2 52.4 52.6 52.4 55 52.2 52.4 52.6 52.4 60 52.3 52.5 52.7 52.5 65 52.3 52.5 52.7 52.5 70 52.3 52.5 52.7 52.5 75 52.3 52.5 52.7 52.5 80 52.3 52.5 52.7 52.5 85 52.3 52.5 52.7 52.5 90 52.3 52.5 52.7 52.5 Tebal isolasi = 2.62 mm I = 11 A Waktu Menit Suhu pengukuran isolasi o C Rata-rata o C 1 2 3 25 25 25 25 5 41.2 40.9 41.6 41.2333 10 42.7 43.2 43.4 43.1 15 44.6 45.6 45.7 45.3 20 45.6 46.5 46.4 46.1667 25 47.5 47.6 47.2 47.4333 30 48.4 48.8 48.9 48.7 35 49.3 49.7 49.6 49.5333 40 49.8 50.7 50.5 50.3333 45 50.6 51.1 50.8 50.8333 50 51 51.4 51.1 51.1667 55 51.2 51.6 51.3 51.3667 60 51.2 51.6 51.5 51.4333 65 51.3 51.7 51.6 51.5333 70 51.3 51.7 51.6 51.5333 75 51.3 51.7 51.6 51.5333 80 51.3 51.7 51.6 51.5333 85 51.3 51.7 51.6 51.5333 90 51.3 51.7 51.6 51.5333 Universitas Sumatera Utara Tebal isolasi = 2.99 mm I = 11 A Waktu Menit Suhu pengukuran inti o C Rata-rata o C 1 2 3 25 25 25 25 5 44.2 43.9 43.8 43.9667 10 45.6 45.4 45.8 45.6 15 46.7 46.5 46.7 46.6333 20 47.3 47.2 47.4 47.3 25 47.9 48.1 47.7 47.9 30 48.4 48.5 48.3 48.4 35 48.8 48.7 48.9 48.8 40 49.1 49.1 49.1 49.1 45 49.3 49.2 49.2 49.2333 50 49.5 49.3 49.2 49.3333 55 49.6 49.4 49.3 49.4333 60 49.7 49.4 49.3 49.4667 65 49.7 49.5 49.4 49.5333 70 49.7 49.5 49.4 49.5333 75 49.8 49.6 49.5 49.6333 80 49.8 49.6 49.5 49.6333 85 49.8 49.6 49.5 49.6333 90 49.8 49.6 49.5 49.6333 Tebal isolasi = 2.99 mm I = 11 A Waktu Menit Suhu pengukuran isolasi o C Rata-rata o C 1 2 3 25 25 25 25 5 39.3 39.5 39.4 39.4 10 41.5 41.4 41.6 41.5 15 42.9 42.9 43 42.9333 20 43.8 43.7 43.8 43.7667 25 44.6 44.7 44.5 44.6 30 45.2 45.4 45.2 45.2667 35 45.6 45.8 45.6 45.6667 40 45.9 46 45.9 45.9333 45 46.2 46.1 46.3 46.2 50 46.4 46.2 46.3 46.3 55 46.5 46.2 46.4 46.3667 60 46.6 46.3 46.4 46.4333 65 46.6 46.3 46.5 46.4667 70 46.7 46.4 46.5 46.5333 75 46.7 46.4 46.5 46.5333 80 46.7 46.4 46.5 46.5333 85 46.7 46.4 46.5 46.5333 90 46.7 46.4 46.5 46.5333 Universitas Sumatera Utara LAMPIRAN B 1. Hasil pengukuran tebal isolasi kabel-1 Titik pengukuran Tebal kabel mm Tebal rata-rata mm 1 2.07 2.07 2 2.07 3 2.06 4 2.07 5 2.08 6 2.06 7 2.06 8 2.08 9 2.08 10 2.07 11 2.07 12 2.07

2. Hasil pengukuran tebal isolasi kabel-2