System Ctr Inputs

Group 16 System Ctr Inputs

The Range/Unit column in the table below shows the allowable parameter values. The text following the table explains the parameters in detail.

Parameter

Range/Unit

Description

2 PARAMETER LOCK

Parameter lock input. 3 PASS CODE

OPEN; LOCKED

Parameter lock pass code. 5 MODIFY MOTOR DATA

Unprotect motor data par's. 6 SHARED MOTION SEL

NO; YES

OFF; ON; FORCE MOT1;

Activate Shared Motion tune.

FORCE MOT2

7 ID RUN DATA SAVE

NO; MOTOR1--GRP81;

Save ID Run if Shared Motion

MOTOR2-GRP82

8 FAN SPD CTRL MODE CONST 50HZ; RUN/STOP; Fan speed control mode CONTROLLED

9 FUSE SWITCH CNTR

Fuse switch control 10 INT CONFIG USER

OFF; ON

Inverter module configuration 11 FB SPEED/TQ CTRL

SPEED; SPEED/TORQUE Enable/Disable torque selection.

2 PARAMETER LOCK

This parameter selects the state of the Parameter Lock. With Parameter Lock you can inhibit unauthorised parameter changes.

OPEN Parameter Lock is open. Parameters can be altered.

LOCKED Parameter Lock is closed from the Control Panel. Parameters cannot be altered. Only entering the valid code at Parameter 16.3 PASS CODE can open the Parameter Lock.

Note: This function is not available if User macros are used.

3 PASS CODE

This parameter selects the Pass Code for the Parameter Lock. The default value of this parameter is 0. In order to open the Parameter Lock change the value to 358. After the Parameter Lock is opened the value is automatically changed back to 0.

5 MODIFY MOTOR DATA

Enable changes to motor parameters. NO

No action YES

Release write protection for motor parameters 99.05-99.08 (protection is set after

a completed ID magn or ID Run).

6 SHARED MOTION SEL

Activate Shared Motion function (see section Shared Motion (80, 81, 82) in chapter Crane Program Description ).

OFF Shared Motion not active

ON Shared Motion activated

FORCE MOT1 Force parameter selection to MOTOR 1

FORCE MOT2 Force parameter selection to MOTOR 2.

7 ID RUN DATA SAVE

Saving of ID Run data when Shared Motion function is used. NO

No action MOTOR1-GRP81

Saves motor model data from ID Run to parameter group 81 for MOTOR 1. MOTOR2-GRP82

Saves motor model data from ID Run to parameter group 82 for MOTOR 2.

8 FAN SPD CRTL MODE

Selection of control mode for the optional speed control of the inverter fan in ACS800 Multidrive.

CONST 50HZ No fan speed control active. Fan is always running with constant nominal 50 or 60 Hz speed.

RUN/STOP Fan is running with constant nominal speed when inverter is modulating and inverter temperature is above min limit.

CONTROLLED Fan speed is controlled between 30 and 110% of nominal depending on inverter temperature.

9 FUSE SWITCH CNTR

Activation parameter for optional inverter DC fuse switch. OFF

The charging logic for DC fuse switch control is disabled. This parameter must be set to OFF if no DC fuse switch is installed.

ON The charging logic for DC fuse switch control is active. This parameter must be set to ON if an optional DC switch is installed.

10 INT CONFIG USER

Adjustable inverter module configuration for n*R8i size inverters. This parameter is user acceptance for Reduced Run (i.e. running with reduced power) function and the number must correspond to the active inverter configuration (number of connected modules) when there are R8i inverter modules removed, e.g. for service. If active inverter configuration is the same as original factory setup than this parameter has no meaning.

11 FB SPEED/TQ CTRL

In fieldbus control mode (Parameter 64.01 STAND ALONE = FALSE): SPEED/TORQUE When set to this value, torque control can be selected with the FB COMMAND

WORD, bit 6 (TORQ CTRL SEL). SPEED When set to this value, the drive is forced to speed control, even if the FB

COMMAND WORD, bit 6 (TORQ CTRL SEL) is set.

12 RESET FAN ON TIME

Resets FAN ON TIME after the fan has been replaced. NO

No action YES

Resets the fan on time to 0