SEQUENCE CONTROL (LOGIC CHART)

Engineering Course

SEQUEN CE CON TROL
( LOGI C CH ART)

PT. Yo ko g a wa Indo ne sia
Wisma Aldiron Dirgantara 2nd floor, suite 202-209
Jl. Jend. Gatot Subroto Kav.72 Jakarta 12780
Phone : 021-799 0102, Fax : 021-799 0070
By I GS – Rev 0.0807

TYPES OF SEQUENCE CONTROL BLOCKS

The following funct ion blocks are cat agorized as sequence
cont rol blocks:
1.Sequence Table Blocks
2.Logic Chart Block
3.Sequent ial Funct ion Chart Block
4.Swit ch I nst rum ent Blocks
5.Sequence Elem ent Blocks
6.Valve Monit oring Block


PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

TYPES OF SEQUENCE CONTROL BLOCKS ( 2/ 2)

LOGIC CHART BLOCK
This funct ion blocks perform s int erlock sequence cont rol program m ed in t he expression
of a logic chart diagram .
The following is t he funct ion block cat agorized as logic chart :
• Logic Chart LC64
Num ber of input elem ent s: 32
Num ber of out put elem ent s: 32
Num ber of logic elem ent s: 64

I n a logic chart block, t he condit ions and operat ions are list ed and t he com binat ion of
condit ions wit h t he logic operat iors corresponding t o t he logic requirem ent m ay
m anipulat e t he operat ion signals. This block can be used as t he descript ion of an
int erlock sequence cont rol or a logic chart .


PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)

( I nput Signal)

( Out put Signal)

Logic chart funct ion block can handle up t o 32 input elem ent s, 32 out put elem ent s
and 64 logic elem ent s/ operat ors ( however, logic elem ent such as W.O, SR/ Flip- Flop,
or CMP is count ed as 2 logic elem ent operat ion.
PT YOKOGAWA INDONESIA
Training Center – Technical Support Group


LOGI C CHART BLOCK ( LC64)
Ge n e r a l Ou t look Of A Logic Cha
Ch a r t
• Pr oce ssin g Tim in g
There ara t wo processing t im ings:
St a r t / Ex e cu t ion Tim in g
I t refers t o t he t im ing at which cont rol algorit hm s
are execut ed when receiving input signals. Select
one of t he following t ype
- Periodic Execut ion ( T)
- One- Shot Processing ( O)
- St art up at I nit ial Cold St art / Rest art of FCS ( I )
- Rest rict ed I nit ial Execut ion ( B)
Out put Tim in g
I t indicat es t he condit ion or behaviour of act ion
signals in conj unct ion wit h t he condit ion signal
st at us change. For logic chart , t he out put t im ing is
fixed t o
- Out put Each Tim e Condit ions Are Sat isfied ( E)


• Sca n Pe r iod
Sequence t able wit h periodic execut ion t ype ( T) is
act ivat ed at defined scan period.
There are t hree t ypes of scan periods:
- Basic Scan ( 1 second – fixed)
- Medium Speed Scan ( 200 & 500 m illiseconds)
50, 100, 250 m illiseconds are also applicable.
- High Speed Scan ( 200 & 500 m illiseconds)
50, 100, 250 m illiseconds are also applicable.

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
St art / Execut ion Tim ing


Periodic Execut ion ( T)
The periodic execut ion m eans t hat t he sequence cont rol block is repeat edly execut ed in a
preset cycle.

One - Shot Execut ion ( O)
When execut ion t im ing of a funct ion block is defined as one- shot t ype, t he block is execut ed
only when it is invoked by ot her funct ion block. A one- shot funct ion block can invoke anot her
one- shot funct ion block. How ever, such succession is lim it ed t o seven blocks. I nvocat ion can
only be init iat ed from t he sam e FCS.
I nvocat ion signal
ACT.ON
I nvoking funct ion
block

ACT.OFF
Sequence process execut ion

Execut ing
One- shot t ype

funct ion block

I dle
One - Shot Pr oce ssing Conce pt ua l D ia gr a m

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
St art / Execut ion Tim ing

I nit ial Execut ion/ Rest art Execut ion ( I )
I n t his execut ion t ype, t he sequence block execut es it s process when t he FCS perform s a cold
st art or a rest art .

Rest rict ed I nit ial Execut ion ( B)
I n rest rict ed init ial execut ion, t he sequence cont rol block execut es only when t he FCS
perform s a cold st art , not include rest art .

PT YOKOGAWA INDONESIA

Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Out put Tim ing

Out put Each Tim e Condit ions Are Sat isfied ( E)
The sequence t able blocks out put it s operat ion/ act ion signal every scan period as long as t he
j udged condit ions are sat isfied.

Condit ion det ect ion
( false or t rue st at e)

True
Condit ion/ input
change

False
Act ion change/ int erupt ion is
not possible as long as t he
condit ion rem ains sat isfied.

True

Act ion/ out put
change

False
“Out put Ea ch Tim e Con dit ions Ar e Sa t isfie d” Con ce pt ua l Figu r e

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s


PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group


LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)

Logic Elem ent s

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Funct ion Blocks and I / O Dat a)
Funct ion blocks t hat can be processed in a sequence t able are shown below.

Sw it ch I nst rum ent Block

Valve Monit oring Block ( VLVM)

Tim er Block ( TM)

Regulat ory Cont rol Blocks

Soft ware Count er Block ( CTS)

Calculat ion Blocks

Pulse Train I nput Count er Block ( CTP)

Faceplat e Blocks

Code I nput Block ( CI )

SFC Blocks

Code Out put Block ( CO)

Unit I nst rum ent Blocks

Relat ional Expression Block ( RL)

Sequence Table Blocks

Resource Scheduler Block ( RS)

Logic Chart Block

I / O dat a t hat can be processed in a sequence t able are shown below.

Processing I / O ( Digit al I nput / Out put )
Soft ware I / O ( I nt ernal Swit ch, Annunciat or, Global Swit ch)
Com m unicat ion I / O

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Swit ch I nst rum ent & Enhanced Swit ch I nst rum ent Blocks) 1/ 2

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Swit ch I nst rum ent & Enhanced Swit ch I nst rum ent Blocks) 2/ 2

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Tim er Block [ TM] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Soft ware Count er Block [ CTS] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Pulse Train I nput [ CTP] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Code I nput Block [ CI ] )

Condit ion Signal Descript ion ( Code Out put Block [ CO] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Relat ional Expression Block [ RL] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Resource Scheduler Block [ RS] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Valve Monit oring Block [ VLVM] )

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Regulat ory Cont rol Block) 1/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Regulat ory Cont rol Block) 2/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Regulat ory Cont rol Block) 3/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Regulat ory Cont rol Block) 4/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Calculat ion Block) 1/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Calculat ion Block) 2/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Calculat ion Block) 3/ 4

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Calculat ion Block) 4/ 4
The t able list s t he calculat ion
blocks t hat can be referenced
in t he condit ion signal as oneshot operat ion.
The form at is:
TAGN AM E.ACT.ON

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Faceplat e Block) 1/ 2

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Faceplat e Block) 2/ 2

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Sequent ial Funct ion Chart Block)
The following list s t he dat a
it em s of SFC block t hat can
describe dat a values in
condit ion specificat ions and
t heir set t ing ranges:
STEPN O:

1 to 99

SW CR[ 5 ] : 0 t o 1 5
SW ST[ 5 ] : 0 ,1
SW OP[ 5 ] : - 1 5 t o 1 5

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Unit Supervision Block)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Processing I / O Block)

Condit ion Signal Descript ion ( Global Swit ch)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Soft ware / Com m on Swit ch)

Condit ion Signal Descript ion ( Com m unicat ion I / O)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LOGI C CHART BLOCK ( LC64)
Condit ion Signal Descript ion ( Annunciat or Message)

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

LABORATORY WORKS
Creat e a logic sequence from t his cont rol narrat ive:
Ca se 1
I n a cascade loop, if t he process variable of t he m ast er cont roller is
High- High alarm t hen t he slave cont roller m ode will have t o swit ch t o
MANUAL m ode and t he m ast er cont roller m ode will have t o swit ch t o
AUTO m ode.
The cont rol m ode of t he slave cont roller cannot be changed unt il t he
alarm vanishes ( process variable is in norm al st at e) .
Condit ion :
Alarm High- High
Act ion :
Mode changes t o Aut o
TI C
101

Condit ion :
Mast er cont r oller alarm high- high
Act ion :
Mode changes t o Manual
Prohibit m ode change if alarm is st ill

Mast er
Cont roller

PI C
101

TT- 1 0 1

Slave
Cont roller

PT- 1 0 1
PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

PV- 1 0 1

LABORATORY WORKS
Creat e a logic sequence from t his cont rol narrat ive:
Ca se 2
I n a cascade loop, if t he process variable of t he m ast er cont roller is
High- High alarm t hen t he slave cont roller m ode will have t o swit ch t o
MANUAL m ode wit h it s out put drops t o MV 25% and t he m ast er
cont roller m ode will have t o swit ch t o AUTO m ode.
However, t he operat or is allowed t o change t he m ode of slave cont roller
t o CASCADE or AUTO m ode even t hough t he process variable is st ill in
High- High alarm st at e.
Condit ion :
Alarm High- High
Act ion :
Mode changes t o Aut o
TI C
101

Condit ion :
Mast er cont r oller alarm high- high
Act ion :
Mode changes t o Manual
Out put ( MV) dr ops t o 25%
Mode change is possible in spit e of alarm

Mast er
Cont roller

PI C
101

TT- 1 0 1

Slave
Cont roller

PT- 1 0 1
PT YOKOGAWA INDONESIA
Training Center – Technical Support Group

PV- 1 0 1

If
If
If
If

PSW
PSW
PSW
PSW

=
=
=
=

0,
1,
2,
3,

MV is
MV =
MV =
MV =

norm al
0% or = MSL
100% or = MSH
PMV

PT YOKOGAWA INDONESIA
Training Center – Technical Support Group