SYST CTRL INPUTS Run Enable, parameter lock etc.
16 SYST CTRL INPUTS Run Enable, parameter lock etc.
16.01 RUN ENABLE Sets the Run Enable signal on, or selects a source for the external Run Enable signal. If Run Enable signal is switched off, the drive will not start or stops if it is
running. The stop mode is set by parameter 21.07 .
YES
1 DI1
Run Enable signal is on.
2 DI2
External signal required through digital input DI1. 1 = Run Enable.
3 DI3
See selection DI1.
4 DI4
See selection DI1.
5 DI5
See selection DI1.
6 DI6
See selection DI1.
7 COMM.CW
See selection DI1.
8 DI7
External signal required through the Fieldbus Control Word (bit 3).
9 DI8
See selection DI1.
10 DI9
See selection DI1.
11 DI10
See selection DI1.
12 DI11
See selection DI1.
13 DI12
See selection DI1.
14 PARAM 16.08
See selection DI1.
Source selected by parameter 16.08 .
16.02 PARAMETER LOCK Selects the state of the parameter lock. The lock prevents parameter changing. OPEN
The lock is open. Parameter values can be changed.
LOCKED Locked. Parameter values cannot be changed from the control panel. The lock 65535
can be opened by entering the valid code to parameter 16.03 .
16.03 PASS CODE Selects the pass code for the parameter lock (see parameter 16.02 ).
0 … 30000 Setting 358 opens the lock. The value reverts back to 0 automatically.
16.04 FAULT RESET SEL Selects the source for the fault reset signal. The signal resets the drive after a fault trip if the cause of the fault no longer exists.
NOT SEL
1 DI1
Fault reset only from the control panel keypad (RESET key).
Reset through digital input DI1 or by control panel:
2 - If the drive is in external control mode: Reset by a rising edge of DI1. - If the drive is in local control mode: Reset by the RESET key of the control
See selection DI1.
4 DI4
See selection DI1.
5 DI5
See selection DI1.
6 DI6
See selection DI1.
7 COMM.CW
See selection DI1.
Reset through the fieldbus Control Word (bit 7), or by the RESET key of the
control panel. Note: Reset through fieldbus Control Word (bit 7) is enabled automatically and
it is independent of parameter 16.04 setting if parameter 10.01 or 10.02 is set
to COMM.CW.
ON STOP Reset along with the stop signal received through a digital input, or by the
RESET key of the control panel.
DI7
10 DI8
See selection DI1.
11 DI9
See selection DI1.
12 DI10
See selection DI1.
13 DI11
See selection DI1.
14 DI12
See selection DI1.
15 PARAM 16.11
See selection DI1.
Source selected by parameter 16.11 .
16.05 USER MACRO IO Enables the change of the User Macro through a digital input. See parameter CHG
99.02 . The change is only allowed when the drive is stopped. During the change, the drive will not start.
Note: Always save the User Macro by parameter 99.02 after changing any parameter settings, or reperforming the motor identification. The last settings saved by the user are loaded into use whenever the power is switched off and on again or the macro is changed. Any unsaved changes will be lost. Note: The value of this parameter is not included in the User Macro. A setting once made remains despite the User Macro change. Note: Selection of User Macro 2 can be supervised via relay output RO3. See
parameter 14.03 for more information.
NOT SEL
1 DI1
User macro change is not possible through a digital input.
Falling edge of digital input DI1: User Macro 1 is loaded into use. Rising edge 2 of digital input DI1: User Macro 2 is loaded into use.
DI2
3 DI3
See selection DI1.
4 DI4
See selection DI1.
5 DI5
See selection DI1.
6 DI6
See selection DI1.
7 DI7
See selection DI1.
8 DI8
See selection DI1.
9 DI9
See selection DI1.
10 DI10
See selection DI1.
11 DI11
See selection DI1.
12 DI12
See selection DI1.
See selection DI1.
16.06 LOCAL LOCK Disables entering local control mode (LOC/REM key of the panel). WARNING! Before activating, ensure that the control panel is not needed for stopping the drive!
OFF
Local control allowed.
ON
Local control disabled.
16.07 PARAMETER SAVE
Saves the valid parameter values to the permanent memory. Note: A new parameter value of a standard macro is saved automatically when changed from the panel but not when altered through a fieldbus connection.
DONE
Saving completed
SAVE..
Saving in progress
16.08 RUN ENA PTR Defines the source or constant for value PAR 16.08 of parameter 16.01 -255.255.31 …
Parameter index or a constant value. See parameter 10.04 for information on - +255.255.31 / C.-
the difference.
32768 … C.32767
16.09 CTRL BOARD
Defines the source of the control board power supply.
SUPPLY Note: If an external supply is used but this parameter has value INTERNAL, the drive trips on a fault at power switch off.
INTERNAL 24V
1 EXTERNAL 24V
Internal (default).
External. The control board is powered from an external supply.
16.10 ASSIST SEL
Enables the Start-up Assistant.
OFF
Assistant disabled.
ON
Assistant enabled.
16.11 FAULT RESET PTR Defines the source or constant for selection PARAM 16.11 of parameter 16.04 . -255.255.31 …
Parameter index or a constant value. See parameter 10.04 for information on - +255.255.31 / C.-
the difference.
32768 … C.32767
16.12 RESET COUNTER
Resets the cooling fan running time counter or kWh counter.
NO
No reset.
FAN ON-TIME Resets the running time counter of the drive cooling fan indicated with 01.44 1