PI BIPOLAR
15 PI BIPOLAR
Selects the source for input I1 of Block Parameter Set 1.
- +255.255.31 / C.-
Parameter index or a constant value:
- Parameter pointer: Inversion, group, index and bit fields. The bit number is 32768 … C.32767
effective only for blocks handling boolean inputs. - Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting. Example: The state of digital input DI2 is connected to Input 1 as follows: - Set the source selection parameter (84.06) to +.01.17.01. (The application
program stores the state of digital input DI2 to bit 1 of actual signal 01.17.) - If you need an inverted value, switch the sign of the pointer value
(-01.17.01.).
84.07 INPUT2
See parameter 84.06 .
- +255.255.31 / C.- 32768 … C.32767
See parameter 84.06 .
84.08 INPUT3
See parameter 84.06 .
- +255.255.31 / C.- 32768 … C.32767
See parameter 84.06 .
84.09 OUTPUT
Stores and displays the output of Block Parameter Set 1.
84.79 OUTPUT
Stores the output of Block Parameter Set 15.
85 USER CONSTANTS
Storage of the Adaptive Program constants and messages. For more information, see the Adaptive Program Application Guide [3AFE64527274 (English)].
85.01 CONSTANT1
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.02 CONSTANT2
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.03 CONSTANT3
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.04 CONSTANT4
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.05 CONSTANT5
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.06 CONSTANT6
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.07 CONSTANT7
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.08 CONSTANT8
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.09 CONSTANT9
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.10 CONSTANT10
Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value 1=1
85.11 STRING1 Stores a message to be used in the Adaptive Program (EVENT block). MESSAGE1
Message
85.12 STRING2 Stores a message to be used in the Adaptive Program (EVENT block). MESSAGE2
Message
85.13 STRING3 Stores a message to be used in the Adaptive Program (EVENT block). MESSAGE3
Message
85.14 STRING4 Stores a message to be used in the Adaptive Program (EVENT block). MESSAGE4
Message
85.15 STRING5 Stores a message to be used in the Adaptive Program (EVENT block). MESSAGE5
Message
90 D SET REC ADDR
- Addresses into which the received fieldbus data sets are written. - Numbers of the main and auxiliary data sets. The parameters are visible only when a fieldbus communication is activated by
parameter 98.02 . For more information, see chapter Fieldbus control .
90.01 AUX DS REF3 Selects the address into which the value of fieldbus reference REF3 is written.
Parameter index
90.02 AUX DS REF4 Selects the address into which the value of fieldbus reference REF4 is written.
Parameter index
90.03 AUX DS REF5 Selects the address into which the value of fieldbus reference REF5 is written.
Parameter index
90.04 MAIN DS SOURCE Defines the data set from which the drive reads the Control Word, Reference REF1 and Reference REF2.
Data set number
90.05 AUX DS SOURCE Defines the data set from which the drive reads References REF3, REF4 and REF5.
Data set number
92 D SET TR ADDR
Main and Auxiliary Data Sets which the drive sends to the fieldbus master station.
The parameters are visible only when a fieldbus communication is activated by parameter 98.02 . For more information, see chapter Fieldbus control .
92.01 MAIN DS STATUS Stores the address from which the Main Status Word is read from. Fixed value, WORD
not visible.
302 (fixed)
Parameter index
92.02 MAIN DS ACT1 Selects the address from which the Actual Signal 1 is read to the Main Data Set.
Parameter index
92.03 MAIN DS ACT2 Selects the address from which the Actual Signal 2 is read to the Main Data Set.
Parameter index
92.04 AUX DS ACT3 Selects the address from which the Actual Signal 3 is read to the Auxiliary Data Set.
Parameter index
92.05 AUX DS ACT4 Selects the address from which the Actual Signal 4 is read to the Auxiliary Data Set.
Parameter index
92.06 AUX DS ACT5 Selects the address from which the Actual Signal 5 is read to the Auxiliary Data Set.
Parameter index
92.07 MSW B10 PTR Selects the address from which the 03.02 Main Status Word bit 10 is read from. -255.255.31 …
Parameter index or a constant value:
+255.255.31 / C.- - Parameter pointer: Inversion, group, index and bit fields. The bit number is 32768 … C.32767
effective only for blocks handling boolean inputs. - Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.
92.08 MSW B13 PTR Selects the address from which the 03.02 Main Status Word bit 13 is read from. -255.255.31 …
Parameter index or a constant value:
+255.255.31 / C.- - Parameter pointer: Inversion, group, index and bit fields. The bit number is 32768 … C.32767
effective only for blocks handling boolean inputs. - Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.
92.09 MSW B14 PTR Selects the address from which the 03.02 Main Status Word bit 14 is read from. -255.255.31 …
Parameter index or a constant value:
+255.255.31 / C.- - Parameter pointer: Inversion, group, index and bit fields. The bit number is 32768 … C.32767
effective only for blocks handling boolean inputs. - Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.