ANALOGUE INPUTS The analogue input signal processing. See section Programmable analogue
13 ANALOGUE INPUTS The analogue input signal processing. See section Programmable analogue
inputs on page 49 .
13.01 MINIMUM AI1 Defines the minimum value for analogue input AI1. When used as a reference, the value corresponds to the reference minimum setting.
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter 11.04 .
0V Zero volts. Note: The program cannot detect a loss of analogue input signal. 1 2V Two volts
2 TUNED VALUE
3 TUNE
The value measured by the tuning function. See the selection TUNE .
The value measurement triggering. Procedure:
- Connect the minimum signal to input. - Set the parameter to TUNE. Note: The readable range in tuning is 0 … 10 V.
13.02 MAXIMUM AI1 Defines the maximum value for analogue input AI1. When used as a reference, the value corresponds to the reference maximum setting.
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter 11.05 .
1 TUNED VALUE
10 V
Ten volts (DC).
2 TUNE
The value measured by the tuning function. See the selection TUNE .
Triggering of the tuning function. Procedure:
- Connect the maximum signal to input. - Set the parameter to TUNE. Note: The readable range in tuning is 0 … 10 V.
13.03 SCALE AI1
Scales analogue input AI1. Example: The effect on speed reference REF1 when:
- REF1 source selection (parameter 11.03 ) = AI1+AI3 - REF1 maximum value setting (parameter 11.05 ) = 1500 rpm - Actual AI1 value = 4 V (40% of the full scale value) - Actual AI3 value = 12 mA (60% of the full scale value) - AI1 scaling = 100%, AI3 scaling = 10%
Scaling range
13.04 FILTER AI1
Defines the filter time constant for analogue input AI1.
Unfiltered Signal
O = I · (1 - e -t/T )
I = filter input (step)
63 O = filter output
Filtered Signal
t = time T = filter time constant
Note: The signal is also filtered due to the signal interface hardware (10 ms time constant). This cannot be changed by any parameter.
0.00 … 10.00 s
Filter time constant
13.05 INVERT AI1
Activates/deactivates the inversion of analogue input AI1.
NO
No inversion
YES Inversion active. The maximum value of the analogue input signal corresponds 65535 to the minimum reference and vice versa.
13.06 MINIMUM AI2
See parameter 13.01 .
0 mA See parameter 13.01 .1
2 TUNED VALUE
4 mA
See parameter 13.01 .
3 TUNE
See parameter 13.01 .
See parameter 13.01 .
13.07 MAXIMUM AI2
See parameter 13.02 .
1 TUNED VALUE
20 mA
See parameter 13.02 .
See parameter 13.02 .2 TUNE
See parameter 13.02 .3
13.08 SCALE AI2
See parameter 13.03 .
See parameter 13.03 .
13.09 FILTER AI2
See parameter 13.04 .
0.00 … 10.00 s
See parameter 13.04 .
13.10 INVERT AI2
See parameter 13.05 .
NO
See parameter 13.05 .
YES
See parameter 13.05 .
13.11 MINIMUM AI3
See parameter 13.01 .
0 mA See parameter 13.01 .1
4 mA See parameter 13.01 .2 TUNED VALUE
3 TUNE
See parameter 13.01 .
See parameter 13.01 .
13.12 MAXIMUM AI3
See parameter 13.02 .
20 mA See parameter 13.02 .1 TUNED VALUE
See parameter 13.02 .2 TUNE
See parameter 13.02 .3
13.13 SCALE AI3
See parameter 13.03 .
See parameter 13.03 .
13.14 FILTER AI3
See parameter 13.04 .
0.00 … 10.00 s
See parameter 13.04 .
13.15 INVERT AI3
See parameter 13.05 .
NO
See parameter 13.05 .
YES
See parameter 13.05 .
13.16 MINIMUM AI5
See parameter 13.01 .
Note: If RAIO-01 is used with voltage input signal, 20 mA corresponds to 10 V.
0 mA See parameter 13.01 .1
2 TUNED VALUE
4 mA
See parameter 13.01 .
3 TUNE
See parameter 13.01 .
See parameter 13.01 .
13.17 MAXIMUM AI5
See parameter 13.02 .
Note: If RAIO-01 is used with voltage input signal, 20 mA corresponds to 10 V.
20 mA See parameter 13.02 .1 TUNED VALUE
See parameter 13.02 .2
TUNE See parameter 13.02 .3
13.18 SCALE AI5
See parameter 13.03 .
See parameter 13.03 .
13.19 FILTER AI5
See parameter 13.04 .
0.00 … 10.00 s
See parameter 13.04 .
13.20 INVERT AI5
See parameter 13.05 .
NO
See parameter 13.05 .
YES
See parameter 13.05 .
13.21 MINIMUM AI6
See parameter 13.01 .
Note: If RAIO-01 is used with voltage input signal, 20 mA corresponds to 10 V.
0 mA
See parameter 13.01 .
2 TUNED VALUE
4 mA
See parameter 13.01 .
3 TUNE
See parameter 13.01 .
See parameter 13.01 .
13.22 MAXIMUM AI6
See parameter 13.02 .
Note: If RAIO-01 is used with voltage input signal, 20 mA corresponds to 10 V.
20 mA See parameter 13.02 .1 TUNED VALUE
See parameter 13.02 .2 TUNE
See parameter 13.02 .3
13.23 SCALE AI6
See parameter 13.03 .
See parameter 13.03 .
13.24 FILTER AI6
See parameter 13.04 .
0.00 … 10.00 s
See parameter 13.04 .
13.25 INVERT AI6
See parameter 13.05 .
NO
See parameter 13.05 .
YES
See parameter 13.05 .
14 RELAY OUTPUTS
Status information indicated through the relay outputs, and the relay operating
delays. See section Programmable relay outputs on page 52 .
14.01 RELAY RO1 OUTPUT Selects a drive status indicated through relay output RO1. The relay energises
when the status meets the setting.
NOT USED
1 READY
Not used.
2 RUNNING
Ready to function: Run Enable signal on, no fault.
3 FAULT
Running: Start signal on, Run Enable signal on, no active fault.
4 FAULT(-1)
Fault
5 FAULT(RST)
Inverted fault. Relay is de-energised on a fault trip.
Fault. Automatic reset after the autoreset delay. See parameter group 31 6