15
SPEKTEK ALAT LABORATORIUM PENGEMBANGAN INDUSTRI TEKNOLOGI KEPOLISIAN KSA T.A. 2011.
4 128 Gbps switching capacity use
5 2 and Layer 3 throughput : 95Mbps
6 Layer 2 features :
7 Maximum MAC addresses per system : 16,000
8 Jumbo frames : 9.216 Bytes
9 Number of VLANs : 4,096
10 Range of possible VLAN IDs : 1 to 4.095
11 2 pieces of 10 GbE SFP optic Ethernet 850nm with a maximum transmission
distance of 300 m 12
Having a management roll-back feature that serves to restore the configuration to a previous configuration
13 Operating System is modular Scalable
14 Letters of support and after-sales from principle
15 security gateways , core switches , distribution switches , and access
switches 1 brand for easy after-sales service , compatibility and interoperability
16 brochure
d. Server Farm switch – 2 units
Server Farm switch must have a minimum specification: 1
24-port 101001000BASE-T 2
Fix 4 - port uplinks can config as port GbE SFP or 10GbE SFP + 3
DRAM: 1 GB ECC, 1 GB Flash, CPU 1Ghz 4
Use 88 Gbps switching capacity 5
Use 88 Gbps switching capacity 6
Layer 2 features : 7
Maximum MAC addresses per system : 32,000 8
Jumbo frames : 9.216 Bytes 9
Number of VLANs : 4,096 10
Range of possible VLAN IDs: 1-4,095 11
Uplink Module 2 - Port 10G SFP + 4 - port 1G SFP 12
2 pieces of 10 GbE SFP optical Ethernet transmission 850nm with a maximum distance of 300m
13 Having a management roll-back feature that serves to restore the configuration to
a previous configuration 14
Operating System is modular Scalable
15 Letters of support and after-sales from principle
16 security gateways , core switches , distribution switches , and access
switches 1 brand for easy after-sales service , compatibility and interoperability
e. Wall mount Rack 15U – 13 units
Wall mount Rack 15U must have a minimum specification: 1
Wall mounted Rack 15U Depth 600mm Double Door 2
includes : 3
1 Units Glass front Door 4
1 Units Back Metal Door 5
2 Units Side Panel 6
1 Units Single Fans 7
1 unit Horizontal Power Distributions 6 Outlets 8
20 Unit Cage Nuts
16
SPEKTEK ALAT LABORATORIUM PENGEMBANGAN INDUSTRI TEKNOLOGI KEPOLISIAN KSA T.A. 2011.
9 4 Unit Dynabolt
10 2 unit wiring management
11 Broshur
f. UPS wallmount Rack – 13 units
UPS must have a minimum specification: 1
input connections using IEC - 320 C14 2
Output connection using IEC - 320 C13 x 6 3
Communication interface using USB , terminal blocks , Intellislot 4
Rack Tower Convertible , including Tower Stand 5
The battery can expand 6
Shutdown monitoring software can be installed on Windows NT2000XPVista , Linux9
7 LED Display
8 Capacity 1500VA 1350watt
9 Power factor 0.9
10 Input Voltage 177 - 280VAC 100 load , 115 - 280VAC 30 Load
11 Input Frequency 40-70Hz
12 Input Protection Type Resettable Circuit Breaker
13 Frequency 50Hz
14 Efficiency of 90 on Line Mode
15 Output can be adjusted in battery mode 220230240VAC
16 Voltage regulation : ± 3
17 Wave Form Pure Sine Wave
18 Battery Type Sealed , non - spillage , maintenance-free , lead acid with 5 year life
time 19
backup time at full load 4 Minutes 20
Recharge time 3 hours to 90 of the specified capacity , after full discharge into resistive load
21 Hot swappable battery
22 Operating Conditions 3,000 meters max. Elevation, 0-90 humidity non -
condensing, 0-40 deg . C 23
The noise level is 45 dBA on Line Mode 24
Online Thermal Dissipation 25
Accessories 26
Supporting SNMP WEB Management Card 27
Supports battery cabinet Extend yes 28
Supporting Service Bypass panel 29
rack mount kit
30 Letters of support and after-sales from principle
31 Letter from the principal availability of spare parts for min. 5 years
32 entire UPS 1 brand for easy after-sales service
3. LIBRARY