Green Building Design Elements

3.1 Green Building Design Elements

Table 2 below shows the integration of several passive green designs that enables the buildings achieve very low energy characteristics. The table shows the different approach but yet still fall under the same passive design features.

Table 2: Green Building Design Elements in the PTMM GEO and LEO building

LEO BUILDING Overview

PTM GREEN ENERGY OFFICE BUILDING

 integrates several passive green design  Active EE system in the building includes innovative air-

 integrates passive green design conditioning system; lighting system; energy efficient  integrates EE active system (ie EE office equipment; EE office appliances; comprehensive energy management

system; as well as mechanical ventilation system

IT Network & server room; EE air conditioning and

 Installed with solar photovoltaic‘s system that generate

ventilation; floor slab cooling; Chilled Metal Ceilings; Ice

Direct Current (DC) and will be diverted to local loads in

storage cooling system; and controls & sensors) the building

 Rainwater harvest system from the secondary roof helps to

reduce water consumption.

Building orientation Façade facing north and south Orientated to the North and the South Sun shading devices  Large overhang at west facing windows

 Larger shading on the eastern façade  Eastern façade does not have any windows or doors facing

 Exterior shading over the windows directly to the east to avoid direct sunlight

Windows design

 Punch hole window façade in the lower floors, and curtain  Double-glazing windows at north and south facing façade  Double-glazing windows and internal blinds at west facing wall windows with exterior shading louvers in the upper

floors. (Figure 5)

 Windows area are about 25-39% of the façade area  50% light transmission and 25% heat transmission  no windows on the western façade but with 12mm thick  See Figure 3a and Table 3

façade

light green tinted glazing

Interior layout

 Open space concept with all the workstation are positioned

 Open space concept, where all the workstations are  Meeting rooms, facility room and stores are located at the

near the windows where daylight is available

concentrated along the border as well as the atrium area in

order to have the maximum daylight  Ground level is reserved for the publics

centre

 Secondary functions are consigned to the inner part, where  Lower ground is mostly consist of M&E rooms, with other artificial lighting is needed.

facilities

Daylight design

 Managed to achieve 65% visible light transmission and  Set to 100% daylight during daytime

allows only 51% of the heat

 Integrates mirror light shelf, roof light and skylight system  Using a combination of exterior shading and tinted glazing

 The atrium allows daylight access to the central of the  See Figure 3b

respectively inside the building

building  See Figure 6

Roof and wall

 Insulated with 200mm aerated concrete block with 15mm

insulation

plaster on both sides, together with light colours on the  Adequate insulation at the roof and wall particularly the

exterior surface

 The envelope of the building uses lightweight concrete  The building is airtight in order to achieve low cold air

western and eastern façade

walls that have an insulation value 2.5 times better than

leakage

that of a conventional brickwall

 100mm thermal insulation in East and West walls; 200mm  Flat roof of the building is 100mm thick reinforced roof insulation, 200mm thermal insulation in ground floor concrete with 50mm thick polystyrene insulation of slab

insulation

 See Figure 4  Canopy roof attached above the roof surface standing as a

secondary roof  Green landscaping along the boundary of the roof Ventilation system  District cooling system; mainly mechanical ventilation  Stack ventilation (Atrium)

Others

 Natural ventilation system in the LEO Building through its  Skylight system; Assisted day lighting thermal flue at the roof top, which creates the thermal

stack effect.  Black painted walls and vents of the thermal flue chimney

(a) (b) Figure 3: The glazing system in GEO building (a) and the daylight design (b)

Figure 4: Roof and wall insulation of GEO Building

Table 3: Typical values of the double-glazing windows

Description U-Value

Heat %

Light % W/m2K

Single

85 85 6 Single, tinted

25 20 5 Double

75 75 3 Double, spectrally selective, low-emissive,

25 50 1 gas filled

Figure 5: Punch hole windows façade of the LEO Building

(a)

(b)

Figure 6: (a) Interior space layout design of GEO Building and (b) The atrium of the building

Dokumen yang terkait

ANALISIS FAKTOR YANGMEMPENGARUHI FERTILITAS PASANGAN USIA SUBUR DI DESA SEMBORO KECAMATAN SEMBORO KABUPATEN JEMBER TAHUN 2011

2 53 20

FAKTOR – FAKTOR YANG MEMPENGARUHI PENYERAPAN TENAGA KERJA INDUSTRI PENGOLAHAN BESAR DAN MENENGAH PADA TINGKAT KABUPATEN / KOTA DI JAWA TIMUR TAHUN 2006 - 2011

1 35 26

A DISCOURSE ANALYSIS ON “SPA: REGAIN BALANCE OF YOUR INNER AND OUTER BEAUTY” IN THE JAKARTA POST ON 4 MARCH 2011

9 161 13

Pengaruh kualitas aktiva produktif dan non performing financing terhadap return on asset perbankan syariah (Studi Pada 3 Bank Umum Syariah Tahun 2011 – 2014)

6 101 0

Pengaruh pemahaman fiqh muamalat mahasiswa terhadap keputusan membeli produk fashion palsu (study pada mahasiswa angkatan 2011 & 2012 prodi muamalat fakultas syariah dan hukum UIN Syarif Hidayatullah Jakarta)

0 22 0

Pendidikan Agama Islam Untuk Kelas 3 SD Kelas 3 Suyanto Suyoto 2011

4 108 178

TAHUN AJARAN 2010 2011

0 6 10

PENGARUH BETA SAHAM, GROWTH OPPORTUNITIES, RETURN ON ASSET DAN DEBT TO EQUITY RATIO TERHADAP VOLUME PERDAGANGAN SAHAM LQ 45 DI BEI PERIODE 2008 – 2011

0 10 64

ANALISIS NOTA KESEPAHAMAN ANTARA BANK INDONESIA, POLRI, DAN KEJAKSAAN REPUBLIK INDONESIA TAHUN 2011 SEBAGAI MEKANISME PERCEPATAN PENANGANAN TINDAK PIDANA PERBANKAN KHUSUSNYA BANK INDONESIA SEBAGAI PIHAK PELAPOR

1 17 40

KOORDINASI OTORITAS JASA KEUANGAN (OJK) DENGAN LEMBAGA PENJAMIN SIMPANAN (LPS) DAN BANK INDONESIA (BI) DALAM UPAYA PENANGANAN BANK BERMASALAH BERDASARKAN UNDANG-UNDANG RI NOMOR 21 TAHUN 2011 TENTANG OTORITAS JASA KEUANGAN

3 32 52