T ROUBLESHOOTING PLC I NPUTS
T ROUBLESHOOTING PLC I NPUTS
If the field device connected to an input module does not seem to turn ON, a problem may exist somewhere between the L1 connection and the terminal connection to the module. An input module’s status indicators can provide information about the field device, the module, and the field device’s wiring to the module that will help pinpoint the problem.
The first step in diagnosing the problem is to place the PLC in standby mode, so that it is not activating the output. This allows the field device to be manually activated (e.g., a limit switch can be manually closed). When the field device is activated, the module’s power status indicator should turn ON, indicating that power continuity exists. If the indicator is ON, then wiring is not the cause of the problem.
Industrial Text & Video Company 1-800-752-8398
www.industrialtext.com
S ECTION Installation PLC Start-Up C HAPTER 6 and Start-Up
and Maintenance 20
The next step is to evaluate the PLC’s reading of the input module. This can
be accomplished using the PLC’s test mode, which reads the inputs and executes the program but does not activate the outputs. In this mode, the PLC’s display should either show a 1 in the image table bit corresponding to the activated field device or the contact’s reference instruction should become highlighted when the device provides continuity (see Figure 20-23). If the PLC is reading the device correctly, then the problem is not located in the input module. If it does not read the device correctly, then the module could be faulty. The logic side of the module may not be operating correctly, or its optical isolator may be blown. Moreover, one of the module’s interfac- ing channels could be faulty. In this case, the module must be replaced.
Input
PLC Monitor
LS1 Status = 1
Figure 20-23. Highlighted contact indicating power continuity.
If the module does not read the field device’s signal, then further tests are required. Bad wiring, a faulty field device, a faulty module, or an improper voltage between the field device and the module could be causing the problem. First, close the field device and measure the voltage to the input module. The meter should display the voltage of the signal (e.g., 120 volts AC). If the proper voltage is present, the input module is faulty because it is not recognizing the signal. If the measured voltage is 10–15% below the proper signal voltage, then the problem lies in the source voltage to the field device. If no voltage is present, then either the wiring or the field device is the cause of the problem. Check the wiring connection to the module to ensure that the wire is secured at the terminal or terminal blocks.
To further pinpoint the problem, check that voltage is present at the field device. With the device activated, measure the voltage across the device using
a voltmeter. If no voltage is present on the load side of the device (the side that connects to the module), then the input device is faulty. If there is power, then the problem lies in the wiring from the input device to the module. In this case, the wiring must be traced to find the problem.
Industrial Text & Video Company 1-800-752-8398
www.industrialtext.com
S ECTION Installation PLC Start-Up C HAPTER 6 and Start-Up
and Maintenance 20
Parts
» An Industrial Text Company Publication Atlanta • Georgia • USA
» C HAPTER T HREE L OGI C C ON CEPT S
» 3 -3 P RINCIPLES OF B OOLEAN A LGEBRA AND L OGIC
» 3 -4 PLC C I RCU I T S AN D L OGI C C ON TACT S Y M BOLOGY
» C ONTACT S YMBOLS U SED IN PLC S
» L OADING C O N S I D E R AT I O N S
» M E M O RY C A PA C I T Y AND U T I L I Z AT I O N
» A P P L I C AT I O N M E M O RY
» D AT A T ABLE O R G A N I Z AT I O N
» 6 -2 I /O R ACK E NCLOSURES AND T ABLE M APPING
» I /O R ACK AND T ABLE M APPING E XAMPLE
» 6 -4 P L C I NSTRUCTIONS FOR D ISCRETE I NPUTS
» 6 -6 P L C I NSTRUCTIONS F OR D ISCRETE O UTPUTS
» 7 -3 A NALOG I NPUT D ATA R E P R E S E N TAT I O N
» 7 -4 A NALOG I NPUT D ATA H ANDLING
» 7 -6 O V E RV I E W OF A NALOG O UTPUT S IGNALS
» 7 -8 A NALOG O UTPUT D ATA R E P R E S E N TAT I O N
» 7 -9 A NALOG O UTPUT D ATA H ANDLING
» C HAPTER E IGHT S PECI AL F U N CT I ON I /O AN D S ERI AL C OM M U N I CAT I ON I N T ERFACI N G
» T HERMOCOUPLE I NPUT M ODULES
» E NCODER /C OUNTER I N T E R FA C E S
» S TEPPER M OTOR I N T E R FA C E S
» S ERVO M OTOR I N T E R FA C E S
» N ETWORK I N T E R FA C E M ODULES
» S ERIAL C O M M U N I C AT I O N
» I N T E R FA C E U SES AND A P P L I C AT I O N S
» 9 -3 L ADDER D IAGRAM F O R M AT
» 9 -5 L ADDER R E L AY P ROGRAMMING L ADDER S CAN E V A L U AT I O N
» P ROGRAMMING N O R M A L LY C LOSED I NPUTS
» 9 -1 0 A RITHMETIC I NSTRUCTIONS
» 9 -1 4 N ETWORK C O M M U N I C AT I O N I NSTRUCTIONS
» L ANGUAGES AND I NSTRUCTIONS
» F UNCTION B LOCK D IAGRAM (FBD)
» S EQUENTIAL F UNCTION C H A RT S (SFC)
» P ROGRAMMING L ANGUAGE N O TAT I O N
» P ROGRAMMING N O R M A L LY C LOSED T RANSITIONS
» D IVERGENCES AND C ONVERGENCES
» -1 C ONTROL T ASK D EFINITION
» C REAT I N G F LOWCH ART S AN D O U T PU T S EQU EN CES
» C ONFIGURING THE PLC S YSTEM
» S PECIAL I NPUT D EVICE P ROGRAMMING
» S IMPLE S TA R T /S TOP M OTOR C IRCUIT
» F O RWA R D /R EVERSE M OTOR I NTERLOCKING
» AC M OTOR D RIVE I N T E R FA C E
» L ARGE R E L AY S YSTEM M O D E R N I Z AT I O N
» A NALOG I NPUT C OMPARISON AND D ATA L INEARIZATION
» A NALOG P OSITION R EADING F ROM AN LV D T
» L INEAR I N T E R P O L AT I O N OF N ONLINEAR I NPUTS
» L ARGE B AT C H I N G C ONTROL A P P L I C AT I O N
» -7 S H O RT P ROGRAMMING E XAMPLES
» -1 B ASIC M EASUREMENT C ONCEPTS D ATA I N T E R P R E TAT I O N
» I NTERPRETING C OMBINED E RRORS
» B RIDGE C IRCUIT T ECHNIQUES
» R ESISTANCE T E M P E R AT U R E D ETECTORS ( RT D S )
» -1 P ROCESS C ONTROL B ASICS
» I N T E R P R E TAT I O N OF E RROR
» T RAN SFER F U N CT I ON S AN D T RAN SI EN T R ESPON SES
» D E R I V AT I V E L APLACE T RANSFORMS
» Out () s = ( )( ) In () s Hp () s
» S ECOND -O RDER L AG R ESPONSES
» D IRECT -A CTING C ONTROLLERS
» T WO -P OSITION D ISCRETE C ONTROLLERS
» T HREE -P OSITION D ISCRETE C ONTROLLERS
» -5 P R O P O RT I O N A L C ONTROLLERS (P M ODE )
» PV () s ( 1 + Hc Hp () s () s ) = SP Hc Hp () s () s () s
» CV () t = K I ∫ 0 Edt + CV ( t = 0 )
» CV ( t = 2 ) = K I 0 Edt + ∫ CV ( t = 1 )
» -7 P R O P O RT I O N A L -I NTEGRAL C ONTROLLERS (PI M ODE )
» -8 D E R I VAT I V E C ONTROLLERS (D M ODE ) S TANDARD D E R I V AT I V E C ONTROLLERS
» -9 P R O P O RT I O N A L -D E R I VAT I V E C ONTROLLERS (PD M ODE )
» -1 2 C ONTROLLER L OOP T UNING
» Z IEGLER –N ICHOLS O PEN -L OOP T UNING M ETHOD
» I TA E O PEN -L OOP T UNING M ETHOD
» S O F T WA R E T UNING M ETHODS
» R ULE -B ASED K NOWLEDGE R E P R E S E N T AT I O N
» S T AT I S T I C A L AND P ROBABILITY A N A LY S I S
» -1 I NTRODUCTION TO F UZZY L OGIC
» -2 H I S T O RY OF F UZZY L OGIC
» -3 F UZZY L OGIC O P E R AT I O N
» F U Z Z I F I C AT I O N C OMPONENTS
» F UZZY P ROCESSING C OMPONENTS
» D E F U Z Z I F I C AT I O N C OMPONENTS
» S YSTEM D ESCRIPTION AND O P E R AT I O N
» M EMBERSHIP F UNCTIONS AND R ULE C R E AT I O N
» IF A = PS AND B = NS THEN C = ZR IF A = PS AND B = NS THEN D = NS
» C HAPTER N INETEEN I /O B US N ET WORK S
» -4 D EVICE B US N ETWORKS B YTE -W IDE D EVICE B US N ETWORKS
» B IT -W IDE D EVICE B US N ETWORKS
» F IELDBUS P ROCESS B US N ETWORK
» P ROFIBUS P ROCESS B US N ETWORK
» I /O B US N ETWORK A DDRESSING
» P ANEL E NCLOSURES AND S YSTEM C OMPONENTS
» -3 N OISE , H E AT , AND V O LTA G E R EQUIREMENTS
» T ROUBLESHOOTING PLC I NPUTS
» -2 P L C S IZES AND S COPES OF A P P L I C AT I O N S
» I NPUT /O UTPUT C O N S I D E R AT I O N S
» C ONTROL S YSTEM O R G A N I Z AT I O N
» E Q U I VA L E N T L ADDER /L OGIC D IAGRAMS
Show more